Subscribe to our newsletter

FLIR A310 f (Automation)

Fixed-Mount Thermal Imaging Camera for Condition Monitoring and Fire Prevention

View Datasheet > A310F

Description

FLIR A310 f thermal camera can be installed almost anywhere to monitor the condition of your critical equipment and other valuable assets. Designed to help safeguard your plant and measure temperature differences, they allow you to see problems before they become costly failures—preventing downtime and enhancing worker safety.

Additional information

Alarm Functions

6 automatic alarms on any selected measurement function, Digital In, Camera temperature, timer

Alarm Output

Digital Out, log, store image, file sending (ftp), email (SMTP), notification

Automatic Heater

Clears window from ice

Base Mounting

TBA

Detector Type

Focal Plane Array (FPA), uncooled microbolometer

Focal Length

76 mm (3.0 in.)

Housing material

Aluminum

IR Resolution

320 × 240 pixels

List of Contents

Cardboard box, Infrared camera with lens and environmental, housing, FLIR Sensors Manager download card, FLIR Tools & Utilities CD-ROM, Lens cap, Printed documentation, Small accessories kit, User documentation CD-ROM

Packaging Size

534 x 207 x 230 mm (21.0 x 8.1 x 9.1 in.)

Set-up Commands

Date/time, Temperature°C/°F

Size (L x W x H)

460 × 140 × 159 mm (18.1 × 5.5 × 6.3 in.)

Spectral Range

7.5–13 µm

Weight

5 kg (11.0 lb.)

Zoom

1–8× continuous, digital, interpolating zooming on images

Digital I/O connector type

6-pole jackable screw terminal

Digital I/O isolation voltage

500 VRMS

Digital I/O supply voltage

12/24 VDC, max 200 mA

Digital input purpose

Image tag (start/stop/general), Input ext. device (programmatically read)

Digital Inputs

2 opto-isolated, 10–30 VDC

Digital Output Purpose

As function of ALARM, Output to ext. device (programmatically set)

Digital Outputs

2 opto-isolated, 10–30 VDC, max 100 mA

Ethernet

Control, result and image

Ethernet Communication

TCP/IP socket-based FLIR proprietary

Ethernet Connector Type

RJ-45

Ethernet Image Streaming

16-bit 320 × 240 pixels @ 7-8 Hz- Radiometric

Ethernet Power

Power over Ethernet, PoE IEEE 802.3af class 0

Ethernet Protocols

Ethernet/IP, Modbus TCP, TCP, UDP, SNTP, RTSP, RTP, HTTP, ICMP, IGMP, ftp, SMTP, SMB (CIFS), DHCP, MDNS (Bonjour), uPnP

Ethernet Standard

IEEE 802.3

Ethernet Type

100 Mbps

Ethernet Video Streaming

MPEG-4, ISO/IEC 14496-1 MPEG-4 ASP@L5

Storage Media

Built-in memory for image storage

Video Out

Composite video output, PAL and NTSC compatible

Video Connector Type

Standard BNC connector

Atmospheric transmission correction

Automatic, based on inputs for distance, atmospheric temperature and relative humidity

Bump

5 g, 11 ms (IEC 60068-2-27)

EMC

EN 61000-6-2 (Immunity), EN 61000-6-3 (Emission), FCC 47 CFR Part 15 Class B (Emission)

Emissivity Correction

Variable from 0.01 to 1.0

Encapsulation

IP 66 (IEC 60529)

Humidity (Operating and Storage)

IEC 60068-2-30/24 h 95% relative humidity +25°C to +40°C (+77°F to +104°F)

Operating Temperature Range

–25°C to +50°C (–13°F to +122°F)

Storage Temperature Range

–40°C to +70°C (–40°F to +158°F)

Vibration

2 g (IEC 60068-2-6)

Color palettes

Color palettes (BW, BW inv, Iron, Rain)

Detector Pitch

25 µm

Detector Time Constant

Typical 12 ms

f-number

1.3

Field of view (FOV)

6° × 4.5°

Focus

Automatic or manual (built in motor)

Image Frequency

30 Hz

Lens Identification

Automatic

Minimum Focus Distance

4 m (13.11 ft.)

Spatial resolution (IFOV)

0.33 mrad

Video Standard

CVBS (ITU-R-BT.470 PAL/SMPTE 170M NTSC)

Accuracy

±4°C (±7.2°F) or ±4% of reading

Area

10 boxes with max./min./average/position (7 if FLIR Sensors Manager is used)

External Optics & Windows Correction

Automatic, based on input of optics/window transmission and temperature

Isotherm

1 with above/below/interval

Measurement Corrections

Global and individual object parameters

Measurement Option

Measurement Mask / Filter Schedule response: File sending (ftp), email (SMTP)

Object Temperature Range

–20 to +120°C (–4 to +248°F) 0 to +350°C (+32 to +662°F)

Optics Transmission Correction

Automatic, based on signals from internal sensors

Reference Temperature

Manually set or captured from any measurement function

Reflected apparent temperature correction

Automatic, based on input of reflected temperature

Spot Meter

10

Thermal Sensitivity/NETD

< 0.05°C @ +30°C (+86°F) / 50 mK

External Power Connector Type

2-pole jackable screw terminal

External Power Connector Type [heater]

2-pole jackable screw terminal

External Power Operation

The camera operates on 12/24 VDC, 9 W max. (allowed range: 10-30 VDC) and heaters on 24 VDC, 25 W max. In total: 34 W.

External Power Operation [heater]

24 VDC, 25 W max.

Voltage

Allowed range 10–30 VDC

Voltage [heater]

Allowed range 21-30 VDC

File Formats

Standard JPEG, 16-bit measurement data included